  • Genset Power Factor: 0.8-3 phase, 1.0-single phase
  • Mechanical/Electronic governor
  • Closed water-cooled
  • Starting batteries( maintenance-Free) with connective wires
  • Color: Weichai blue (B,F)/beige canopy and black chassis (L)
  • WPG50-96
Weichai Power Co., Ltd.

Weichai Power Co., Ltd.

Since:

1946

You May Also Like

Product Detail Parameters

Model WPG50-96 Frequency 60Hz
Standby Rating (kVA) 63 Standby Rating (KW) 50
Prime Rating (kVA) 56 Prime Rating (KW) 45
Engine Model WP4D66E201

International Standard Number

WPG50-96

Product Description

Gen-Set Specifications

Genset Model WPG50*96
Power Factor0.8-3 phase, 1.0-single phase
FrequencyStandby RatingPrime Rating
 kVAkWkVAkW
60Hz63505645
B-SeriesStandard≤102 dB(A)
F-SeriesWith base fuel tank ≤102 dB(A)
L-SeriesWith base fuel tank and soundproof enclosure≤75 dB(A)@7m
   

Standard Features

♦ Mechanical/Electronic governor♦DC24 Electric starter♦ Deep-sea 6020
♦ Closed water-cooled♦IP23♦H type insulation
 Air filter, muffler ♦ Circuit Breaker
♦Starting batteries( maintenance-Free) with connective wires♦Battery Charger
♦Oil Drain Valve♦Forklift Groove♦Shock Absorber
♦Color: Weichai blue (B,F)/beige canopy and black chassis (L)♦Documents
♦Packaging: wooden packing case(B,F)

Options

◇Automatic Main Failure(AMF)◇Automatic Transfer Switch(ATS)◇paralleling system
◇External fuel tank◇Engine Heater (water &oil heater)◇Spare Parts/ Special tool

 

Engine Specifications

Engine Make & ModelWeichai   WP4D66E201
Design4 cycle, in-line, Turbocharged
Rated Speed1800 rpm
Prime Power60kW
Standby Power66 kW
Bore & Stroke105x130mm
Displacement4.5L
Cylinder Number4
Battery Capacity2X60A.h
Starting Method24V electric starter and battery charging alternator
Fuel systemDirect injection
Fuel consumption (l/hr) 
Prime110% Load100% Load75% Load50% Load
60kW16.214.5117.7
Air Cleaner TypeDry replaceable element with restriction indicator
Lube Oil Filter TypeSpin on full flow filer
Volume of oil pan (L)10
Standard cooling system45℃ ambient radiator
Coolant capacity(L)18

Alternator Specifications

Alternator MakeStamford/Leroy-somer/Xingnuo
Alternator ModelUC224D/LSA 42.3 M8/XN224D
DesignBrushless single bearing, revolving field
Stator2/3 pitch
RotorSingle bearing, flexible disc
Exciter TypeSelf Excited
Insulation SystemClass H
   Protection                  IP23
Winding Way12
Voltage Regulation≤±1%

Dimensions

 LengthWidthHeightWeight
B-Series20100 mm950 mm1350 mm1095 kg
L-Series2600 mm1050 mm1830 mm1445 kg

 

Remarks

 

Prime Rating: These ratings are applicable for supplying continuous electrical power (at variable load) in the lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

Standby Rating: These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous tested (as defined in ISO 8528‐3).

Standard Reference Conditions

Note: Standard reference conditions 25℃(77℉)Air Inlet Temp, 100m(328 ft) A.S.L. 30% relative humidity.

Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.