{{i.title_en}}
WEICHAI WPG180B86NG Series 60Hz/180KWe Gas Generator Set
MOQ: 1 PCS
Note: If you have any questions,please contact us
- High reliability, low emissions, low noise
- Have kinds of domestic product certification and CE certification
- By using electronic control technology, the emission meets the national emission standard III
- WPG180B86NG
Weichai Power Co., Ltd.
Since:
1946
Product Description
180KWe GAS gen-set data sheet
Gen-set Specification | |
Model | WPG180B86NG |
Prime | 180kWe/ 225kVA |
Standby | 180kWe/ 225kVA |
Voltage/ Frequency | 480V/ 60Hz |
Power Factor | 0.8- 3 Phases |
Emission | China State 3/ EU Stage 3A |
Noise level dB(A) | B Series: ≤102 L Series: ≤75 @7m |
Standard Configurations | ||
♦ Proven ECM and gas intake system | ♦ IP23 | ♦ DeepSea 6020 Controller |
♦ DC24 electric starter& alternator | ♦ H type insulation | ♦ Legrand Circuit Breaker |
♦ Puller type fan with Radiator | ♦ Air filter& muffler | ♦ NG Shutoff valve |
♦ Maintenance-Free batteries w/ wires | ♦Battery Charger | ♦Oil Drain Valve |
♦ Forklift Groove Skid with Shock Absorber | ||
Options | ||
² Automatic Main Failure (AMF) | ² paralleling system panel | ² Sound Proof Enclosure |
² Automatic Transfer Switch (ATS) | ² Telematics kit | ² Trailer type station |
² Jacket water &oil heater kit | ² LPG vapor kit | ² Spare Parts/ Special tool |
² H2S Purification System Packing | ² CHP System Packing |
Engine Technical Data
Base Data Model: WP10D238E301NG NO. of Cylinders: 6 Type: In-Line ,4 Stroke Aspiration: TA Cooling Method: Water Governing Type: ECM control Compression ratio: 11.5:1 Fuel Type: Natural Gas Emission: China State 3/ EU Stage 3A |
Displacement: 9.7L Bore/Stroke: 126/130mm Electric system: DC24V Outline Dimension: 2006×859×1396 mm Dry weight: 850kg Prime Power: 216kW Standby Power: 216kW Rated NG Fuel Consumption: 56m3/h Speed in Stability: <5% |
Lubrication System Oil filter control method: Full flow type Total Oil Capacity: 19L Oil Type: CF15W/40 | Gas System Recommended Gas: Pipeline gas or natural gas (methane≥70%, sulfur content ≤20 mg/m3) Gas pressure: 3~7 kPa |
Air System Air Filter Type: Dry-type Max. Air Intake Restriction: ≤6 kPa Recommended air filter mass flow: 760 kg/h | Exhaust System Silencer type : horizontal Silencer Noise Reduction Level: 15 dB(A) Exhaust Gas Temperature °C: ≤650 |
Cooling System Coolant Capacity: 35L |
Water pump type: Centrifugal |
Alternator Technical Data
Physical Data Manufacturer: Stamford/ Leroy-somer Model: UC274H/LSA 46.3 S3 NO. of bearing: 1 Insulation Class: H Steady Voltage Regulation: ≤±2.5% |
Ingress Protection Rating: IP23 Winding Pitch-code: 2/3 Wire: 12 Excitation: Brushless Rated Power Factor: 0.8 |
Control Module Specifications
The DSE6020 is an Auto Mains Failure Control Module
♦ Back-lit LCD display
♦ 3 Phase generator and 3 Phase Mains monitoring
♦ Monitoring speed, frequency, voltage, current, oil pressure, coolant temperature and fuel level
♦ Display warning, shutdown and engine status information
♦ Hours counter provides accurate information for monitoring and maintenance
Gen-set Dimensions & Weights
Length | Width | Height | Weight | |
B-Series | 2980mm | 1280mm | 1780 mm | 2140 kg |
L-Series | 3900 mm | 1350 mm | 2050 mm | 3050 kg |
Remark
Standby Rating:
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous tested (as defined in ISO 8528-3).
Prime Rating:
These ratings are applicable for supplying continuous electrical power (at variable load) in the lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.